diff --git a/CHANGELOG.md b/CHANGELOG.md
index 9e000000a..df6f20278 100644
--- a/CHANGELOG.md
+++ b/CHANGELOG.md
@@ -17,8 +17,7 @@ and this project adheres to [Semantic Versioning](https://semver.org/spec/v2.0.0
- set boiler warm water temp on Junkers/Bosch HT3
### Changed
-
-- improved MQTT publishing to stop flooding
+- improved MQTT publishing to stop flooding. `publish_time` must be at least 1 (second)
### Removed
- `autodetect scan`
diff --git a/README.md b/README.md
index 3d58fb72c..ad79ab171 100644
--- a/README.md
+++ b/README.md
@@ -1,5 +1,4 @@
-
-# EMS-ESP
+
[](https://github.com/proddy/EMS-ESP/blob/master/CHANGELOG.md)
[](https://github.com/proddy/EMS-ESP/commits/master)
@@ -10,12 +9,14 @@
[](https://github.com/proddy/EMS-ESP/releases)
[](https://gitter.im/EMS-ESP/community)
+
+-------------
EMS-ESP is a open-source system to communicate with **EMS** (Energy Management System) based boilers, thermostats and other modules from manufacturers like Bosch, Buderus, Nefit, Junkers and Sieger.
The code is written for the Espressif **ESP8266** microcontroller and supports a telnet console for real-time monitoring and configuration and customizable MQTT support for publishing the information to a home automation system such as Home Assistant or Domoticz.
-#### Please reference the [Wiki](https://github.com/proddy/EMS-ESP/wiki) for further details and instructions on how to build and configure the firmware.
+#### Please reference the [Wiki](https://emsesp.github.io/docs) for further details and instructions on how to build and configure the firmware.
---
@@ -23,31 +24,28 @@ The code is written for the Espressif **ESP8266** microcontroller and supports a
#### A web interface for easy configuration and real-time monitoring of the EMS bus
-|  |  |
+|  |  |
| -------------------------------------------------------- | ---------------------------------------------------------- |
#### MQTT support for Home Assistant and Domoticz
-
+
#### Telnet for advanced configuration and verbose traffic logging
-|  |  |
+|  |  |
| ------------------------------------------------------------ | -------------------------------------------------------- |
## Supported EMS devices
-More than **50** EMS devices are currently supported. See the [complete list](https://github.com/proddy/EMS-ESP/wiki/Supported-EMS-Devices) from the [Wiki](https://github.com/proddy/EMS-ESP/wiki).
+More than **50** EMS 1.0 and 2.0 devices are currently supported. See the [complete list](https://proddy.github.io/EMS-ESP/#/Supported-EMS-Devices).
-## Uploading the firmware
-Latest stable firmware build can be found [here](https://github.com/proddy/EMS-ESP/releases/latest).
+---
-Follow [these instructions](https://github.com/proddy/EMS-ESP/wiki/Building-and-Uploading-the-Firmware) on how to upload to the ESP8266.
+## Native compatibility with bbqkees' **EMS Gateway**
-## Compatible with bbqkees' EMS Gateway
+All firmware versions fully support BBQKees' [EMS Gateway](https://bbqkees-electronics.nl/) board with integrated Wemos D1 ESP8266.
-The firmware fully supports BBQKees' [EMS Gateway](https://shop.hotgoodies.nl/ems/) board with integrated Wemos D1 ESP8266.
-
-|  |  |  |
+|  |  |  |
| ------------------------------------------------------------------------------------------ | ------------------------------------------------------------------------------------ | ---------------------------------------------------------------------------------------------------- |
diff --git a/doc/ems gateway/logo-proddy-fw.jpg b/doc/ems gateway/logo-proddy-fw.jpg
deleted file mode 100644
index 3f0d7c36f..000000000
Binary files a/doc/ems gateway/logo-proddy-fw.jpg and /dev/null differ
diff --git a/doc/ems references/HT3-Bus_Telegramme.html b/doc/ems references/HT3-Bus_Telegramme.html
deleted file mode 100644
index 1a019762c..000000000
--- a/doc/ems references/HT3-Bus_Telegramme.html
+++ /dev/null
@@ -1,7862 +0,0 @@
-
-
-
-
| HT Bus-Telegramme | -||||
| Datum: | -14.10.2016 | -|||
| Version: | -0.2.0 | -|||
| Message-ID | -Telegramm(hex) | -Beschreibung | -Source-Werte (hex) | -Bemerkung | -
| (SO) | -||||
| 2 | -SO TT 02 xy | -Software-Version / Busteilnehmer | -88 | -TT = <Target-/Token-Nr> | -
| 7 | -SO 00 07 xy | -Steuerung: EMS Token Status | -88 | -|
| 6 | -SO 00 06 xy | -Datum / Zeit | -90 | 98 | -Mit 14 und 17 Bytes Länge | -
| 190 | -TT 00 BE xy | -ErrorCode / DisplayCode von Target | -TT = <Target-/Token-Nr> | -|
| 24 | -SO 00 18 xy | -Heizgerät: Kesseldaten | -88 | -Mit 31 und 33 Bytes Länge | -
| 25 | -SO 00 19 xy | -Heizgerät: Heizungsdaten | -88 | -|
| 188 | -SO 00 BC xy | -Heizgerät: Hybrid (Wärmepumpe) | -||
| 27 | -SO 00 1B xy | -Sollwert Warmwasser | -90 | -|
| 51 | -SO 00 33 xy | -Warmwasser: Daten von Steuerung | -88 | -|
| 52 | -SO 00 34 xy | -Warmwasser: Daten von Steuerung | IPM | -88 | Ax (x:=0...7) | -Mit 22,23 und 25 Bytes Länge | -
| 467...468 | -SO 00 FF xy 00 D3...D4 | -Betriebsart WW-System | -90 | -|
| 26 | -SO 08 1A xy | -Heizkreis: Systemwerte | -90 | -|
| 268 | -SO 00 FF xy 00 0C | -Heizkreis: von IPM1/IPM2 für Mischer | -Ax (x:=0...7) | -|
| 296 | -SO 00 FF xy 00 28 | -Heizkreis: Fehlermeldungen | -90 | -|
| 357...366 | -SO 00 FF xy 00 65...6E | -Heizkreis: Bauart1 | -90 | -|
| 367...376 | -SO 00 FF xy 00 6F...78 | -Heizkreis: Temperaturniveau | -90 | 9x (x:=8...F) | -|
| 377...386 | -SO 00 FF xy 00 79...82 | -Heizkreis: Bauart2 | -90 | -|
| 677...684 | -SO 00 FF xy 01 A5...AC | -Heizkreis: Systemwerte | -90 | 98 | -Cxyz-Controller (z.B. CW100) | -
| 259 | -SO 00 FF xy 00 03 | -Solar: Solardaten von ISM1 | -B0 | -|
| 260 | -SO 00 FF xy 00 04 | -Solar: Solardaten von ISM2 | -B0 | -Mit 24 und 35 Bytes Länge | -
| 866 | -SO 00 FF xy 02 62 | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 868 | -SO 00 FF xy 02 64 | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 873 | -SO 00 FF xy 02 69 | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 874 | -SO 00 FF xy 02 6A | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 910 | -SO 00 FF xy 02 8E | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 913 | -SO 00 FF xy 02 91 | -Solar: Solardaten von MS100 | -B0 | -EMS2-Bus | -
| 357_14...366_14 | -SO TA FF 0E 00 65...6E | -Modem-CMD: Betriebsart setzen | -8D | C8 | -TA = <Target-Nr> | -
| 377_4 ...386_4 | -SO TA FF 04 00 79...82 | -Modem-CMD: Betriebsart setzen | -8D | C8 | -TA = <Target-Nr> | -
| 357_17...366_17 | -SO TA FF 11 00 65...6E | -Modem-CMD: Temp-Niveau setzen | -8D | C8 | -TA = <Target-Nr> | -
| 377_7 ...386_7 | -SO TA FF 07 00 79...82 | -Modem-CMD: Temp-Niveau setzen | -8D | C8 | -TA = <Target-Nr> | -
| 1: ( Hi-Byte * 256 + Lo-Byte ) / 10 | -Calculation-Type: 1 | -|||
| 2: ( Byte3 * 65536 + Byte2 * 256 + Byte1 ) | -Calculation-Type: 2 | -|||
| 3: ( Byte4 * 1048576 + Byte3 * 65536 + Byte2 * 256 + Byte1 ) | -Calculation-Type: 3 | -|||
| 4: ( Type 3 ) / 10 | -Calculation-Type: 4 | -|||
| 5: ( Type 3 ) / 1000 | -Calculation-Type: 5 | -|||
| HT Bus-Telegramme | -||||
| Message-ID: 2_x_0 | -||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -Beispiel (Hex) | -
| 16Byte | -||||
| Telegramm: Software-Version / Busteilnehmer | -||||
| 0 | -SO | -Source | -88 | -|
| 1 | -TT | -<Token-/Target-Nr> (Geräteadr. Ungleich 0) | -Target | -18 | -
| 2 | -02 | -2_x_0 | -02 | -|
| 3 | -xy | -Telegramm-Offset (hier 0...9). | -00 | -|
| 4 | -xy | -Erste Erkennung Busteilnehmer | -2_0_0 | -5F | -
| - 00 = Variantenerkennung in Betrieb oder fehlerhaft | -||||
| ….. | -||||
| - 5F = Heatronic III | -||||
| - 64 = Schaltmodul IPM1 | -||||
| - 65 = Solarmodul ISM1 | -||||
| - 66 = Schaltmodul IPM2 | -||||
| - 67 = Solarmodul ISM2 | -||||
| - 67 = Solarmodul ISM2 | -||||
| - 69 = Witterungsgeführter Regler FW100 | -||||
| - 6A = Witterungsgeführter Regler FW200 | -||||
| - 6B = Raumtemperaturregler FR100 | -||||
| - 6C = Raumtemperaturregler FR110 | -||||
| - 6D = Fernbedienung FB 10 | -||||
| - 6E = Fernbedienung FB100 | -||||
| - 6F = Raumtemperaturregler FR10 | -||||
| ….. | -||||
| - BD = KM200 | -||||
| - BF = Raumtemperaturregler FR120 | -||||
| - C0 = Witterungsgefuehrter Regler FW120 | -||||
| ….. | -||||
| 5 | -xy | -Software-Familie | -2_1_0 | -22 | -
| 6 | -xy | -Version der Softwarefamilie | -2_2_0 | -04 | -
| 7 | -xy | -Zweite Erkennung Busteilnehmern | -2_3_0 | -00 | -
| 8 | -xy | -Kennzahl f. Grosse Änderung in HW- und SW | -2_4_0 | -00 | -
| 9 | -xy | -Kennzahl f. Kleine Änderung in HW- und SW | -2_5_0 | -00 | -
| 10 | -xy | -Dritte Erkennung Busteilnehmern | -2_6_0 | -00 | -
| 11 | -xy | -Kennzahl f. Kleine Änderung in HW- und SW | -2_7_0 | -00 | -
| 12 | -xy | -Kennzahl f. Grosse Änderung in HW- und SW | -2_8_0 | -00 | -
| 13 | -xy | -Markenidentifizierung | -2_9_0 | -00 | -
| - 00 = keine Markenerkennung | -||||
| - 01 = Bosch | -||||
| - 02 = Junkers | -||||
| - 03 = Buderus | -||||
| ….. | -||||
| 14 | -<CRC> | -CRC | -63 | -|
| 15 | -<Ende> | -Ende | -00 | -|
| HT Bus-Telegramme | -|||
| Message-ID: 7_x_y | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 21Byte | -|||
| EMS Token Status | -|||
| 0 | -SO | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -07 | -7_x_y | -|
| 3 | -xy | -Telegramm-Offset (hier 0...14). | -|
| 4 | -Bit0...Bit7 | -EMS Token Status 8: EMS Master | -7_0_0 bis | -
| - EMS Token Status 9 … 15 | -7_0_7 | -||
| 5 | -Bit0...Bit7 | -EMS Token Status 16 … 23 | -7_1_0 bis | -
| 7_1_7 | -|||
| 6 | -Bit0...Bit7 | -Busadresse 24 vorhanden | -7_2_0 bis | -
| - EMS Token Status 25 … 31 | -7_2_7 | -||
| 7 | -Bit0...Bit7 | -Busadresse 32:Mischerstellmotor im HK1 vorhanden | -7_3_0 bis | -
| - EMS Token Status 33 … 39 | -7_3_7 | -||
| 8 | -Bit0...Bit7 | -Busadresse 40:Warmwassersystem im HK1 vorhanden | -7_4_0 bis | -
| - EMS Token Status 41 … 47 | -7_4_7 | -||
| 9 | -Bit0...Bit7 | -Busadresse 48:Solarmodul vorhanden | -7_5_0 bis | -
| - EMS Token Status 49 … 55 | -7_5_7 | -||
| 10 | -Bit0...Bit7 | -Busadresse 56:Fernbedienung f. HK1 vorhanden | -7_6_0 bis | -
| - EMS Token Status 57 … 63 | -7_6_7 | -||
| 11 | -Bit0...Bit7 | -Busadresse 64:Temperaturfühler im HK1 vorhanden | -7_7_0 bis | -
| - EMS Token Status 65 … 71 | -7_7_7 | -||
| 12 | -Bit0...Bit7 | -Status für Busadresse 72...79 | -7_8_0 bis | -
| 7_8_7 | -|||
| 13 | -Bit0...Bit7 | -EMS Token Status 80 … 87 | -7_9_0 bis | -
| 7_9_7 | -|||
| 14 | -Bit0...Bit7 | -EMS Token Status 88 … 95 | -7_10_0 bis | -
| 7_10_7 | -|||
| 15 | -Bit0...Bit7 | -EMS Token Status 96 … 103 | -7_11_0 bis | -
| 7_11_7 | -|||
| 16 | -Bit0...Bit7 | -EMS Token Status 104 … 111 | -7_12_0 bis | -
| 7_12_7 | -|||
| 17 | -Bit0...Bit7 | -EMS Token Status 112 … 119 (Cascaded EMS) | -7_13_0 bis | -
| 7_13_7 | -|||
| 18 | -Bit0...Bit7 | -EMS Token Status 120 … 127 (Cascaded EMS) | -7_14_0 bis | -
| 7_14_7 | -|||
| 19 | -<CRC> | -CRC | -|
| 20 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -||||
| Message-ID:6_x_y | -||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -|
| 14Byte | -17Byte | -|||
| Datum/Zeit – Telegramm | -||||
| 0 | -90 | 98 | -90 | 98 | -Source :=90h oder :=98h | -Source | -
| 1 | -00 | -00 | -Target | -|
| 2 | -06 | -06 | -6_x_y | -|
| 3 | -xy | -xy | -Telegramm-Offset (hier 0...6|10). | -|
| 4 | -xy | -xy | -Jahr (Wert + 2000)dez. | -6_0_0 | -
| 5 | -xy | -xy | -Monat (01 … 12)dez. | -6_1_0 | -
| 6 | -xy | -xy | -Stunden (00 … 23)dez. | -6_2_0 | -
| 7 | -xy | -xy | -Tag (01 … 31)dez. | -6_3_0 | -
| 8 | -xy | -xy | -Minute (00 … 59)dez. | -6_4_0 | -
| 9 | -xy | -xy | -Sekunde (00 … 59)dez. | -6_5_0 | -
| 10 | -xy | -xy | -Wochentag | -6_6_0 | -
| 01=Montag; 02=Dienstag;... für Fxyz – Regler | -||||
| 00=Montag; 01=Dienstag;... für Cxyz – Regler | -||||
| 11 | -Bit0...Bit7 | -Bit0...Bit7 | -Uhrstatus | -|
| Bit0 | -Bit0 | -- Sommerzeit | -6_7_0 | -|
| Bit1 | -Bit1 | -- Funkempfang vorhanden | -6_7_1 | -|
| Bit2 | -Bit2 | -- Funksignal vorhanden | -6_7_2 | -|
| Bit3...Bit7 | -Bit3...Bit7 | -- Immer 0 | -||
| 12 | -<CRC> | -xy | -Token-Adresse des aktuellen RTC-Owner | -6_8_0 | -
| 13 | -<Ende> | -xy | -Automatische Sommer/Winter Umschaltung | -6_9_0 | -
| 14 | -xy | -RTC Benutzer Kalibierungswert | -6_10_0 | -|
| 15 | -<CRC> | -|||
| 16 | -<Ende> | -|||
| HT Bus-Telegramme | -|||
| Message-ID: 190_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 11Byte | -|||
| ErrorCode von Target-/Token | -|||
| 0 | -TT | -Target-/Token Nummer | -Source | -
| 1 | -00 | -- 00 = An Alle | -Target | -
| 2 | -BE | -190_x_0 | -|
| 3 | -00 | -Immer 0 | -|
| 4 | -xy | -Bus-Adresse des Fehlercodes | -190_0_0 | -
| 5 | -Hi-Byte | -Displaycode | -190_1_0 | -
| 6 | -Lo-Byte | -||
| 7 | -Hi-Byte | -Cause Code | -190_3_0 | -
| 8 | -Lo-Byte | -||
| 9 | -<CRC> | -CRC | -|
| 10 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -||||
| Message-ID:24_x_y | -||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -|
| 31Byte | -33Byte | -|||
| Kessel-Telegramm: Heizgerät | -||||
| 0 | -88 | -88 | -Source | -|
| 1 | -00 | -00 | -Target | -|
| 2 | -18 | -18 | -24_x_y | -|
| 3 | -xy | -xy | -Telegramm-Offset (hier 0...25). | -|
| 4 | -xy | -xy | -Vorlauf Soll-Temperatur | -24_0_0 | -
| 5 | -Hi-Byte | -Hi-Byte | -Vorlauf Ist-Temperatur | -24_1_0 | -
| 6 | -Lo-Byte | -Lo-Byte | -||
| 7 | -xy | -xy | -Kessel maximale Leistung (76/84/100; 100)% | -24_3_0 | -
| 8 | -0-100 | -0-100 | -Aktuelle Brennerleistung in % | -24_4_0 | -
| 9 | -Bit0...Bit7 | -Bitfeld | -Betriebsmode | -|
| Bit0 | -Bit1 | -- Heizungs-Mode | -24_5_0 | -|
| Bit1 | -Bit2 | -- Warmwasser-Mode | -24_5_1 | -|
| Bit2 | -Bit3:=0 | -- Status Servicebetrieb | -24_5_2 | -|
| Bit3 | -Bit4 | -- Brennerflamme an | -24_5_3 | -|
| Bit4 | -Bit5:=0 | -- Aufheizphase des Wärmeerzeugers | -24_5_4 | -|
| Bit5 | -Bit6:=0 | -- Verriegelnder Fehler | -24_5_5 | -|
| Bit6 | -Bit7:=0 | -- Blockierender Fehler | -24_5_6 | -|
| Bit7 | -Bit8:=0 | -- Status Wartungsanforderung | -24_5_7 | -|
| 10 | -Bit0...Bit7 | -Bit0...Bit7 | -Status Heizbetrieb | -|
| Bit0 | -Bit0 | -- Heizbetrieb im Bussystem | -24_6_0 | -|
| Bit1 | -Bit1 | -- Wärmeanforderung (durch Schalter) | -24_6_1 | -|
| Bit2 | -Bit2 | -- Wärmeanforderung bei Betriebsart: Frost | -24_6_2 | -|
| Bit3 | -Bit3 | -- Wärmeanforderung im WW-Betrieb bei Betriebsart: Frost | -24_6_3 | -|
| Bit4 | -Bit4 | -- Interne Wärmeanforderung bei WW | -24_6_4 | -|
| Bit5 | -Bit5 | -- Wärmeanforderung f. WW-Erkennung im Bussystem | -24_6_5 | -|
| Bit6 | -Bit6 | -- Wärmeanforderung | -24_6_6 | -|
| Bit7 | -Bit7 | -- Wärmeanforderung im Testmodus | -24_6_7 | -|
| 11 | -Bit0...Bit7 | -Bit0...Bit7 | -Betriebs-Status | -|
| Bit0 | -Bit0 | -- Brenner an (Relais-Signal erste Brennstufe) | -24_7_0 | -|
| Bit1 | -Bit1 | -- Brenner an (Relais-Signal zweite Brennstufe) | -24_7_1 | -|
| Bit2 | -Bit2 | -- Lüfter an (Relais-Signal f. Lüfter) | -24_7_2 | -|
| Bit3 | -Bit3 | -- Zündung an (Relais-Signal f. Zündung) | -24_7_3 | -|
| Bit4 | -Bit4 | -- Ölvorwärmer an (Relais-Signal f. Ölvorwärmer) | -24_7_4 | -|
| Bit5 | -Bit5 | -- Heizungspumpe an (Relais-Signal f. HP) | -24_7_5 | -|
| Bit6 | -Bit6 | -- 3-Wege-Ventil auf Speicherladung | -24_7_6 | -|
| Bit7 | -Bit7 | -- Zirkulationspumpe an (Relais-Signal f. ZP) | -24_7_7 | -|
| 12 | -Bit0...Bit7 | -Bit0...Bit7 | -Status 1 | -|
| Bit0 | -Bit0 | -- Meldesignal Abgasklappe f. Freigabe Ölbrenner | -24_8_0 | -|
| Bit1 | -Bit1 | -- Signal vom Luftdruckschalter | -24_8_1 | -|
| Bit2 | -Bit2 | -- Signal vom Flüssiggasbrenner | -24_8_2 | -|
| Bit3 | -Bit3 | -- Signal vom Gasdruckwächter | -24_8_3 | -|
| Bit4 | -Bit4 | -- Signal vom externen Ein-/Aus-Schalter | -24_8_4 | -|
| Bit5 | -Bit5 | -- Digitales Eingangssignal | -24_8_5 | -|
| Bit6 | -Bit6 | -- Signal vom Sicherheitstemperaturbegrenzer (TB) | -24_8_6 | -|
| Bit7 | -Bit7 | -- Signal vom Raumthermostat | -24_8_7 | -|
| 13 | -Hi-Byte | -Hi-Byte | -WW-Temperatur Speicherfühler1 | -24_9_0 | -
| 14 | -Lo-Byte | -Lo-Byte | -- (0x8300 := Nicht vorhanden) | -|
| 15 | -Hi-Byte | -Hi-Byte | -WW-Temperatur Speicherfühler2 | -24_11_0 | -
| 16 | -Lo-Byte | -Lo-Byte | -- (0x8000 | 0x7D00 := Nicht vorhanden) | -|
| 17 | -Hi-Byte | -Hi-Byte | -Temperatur Kessel-Rücklauf | -24_13_0 | -
| 18 | -Lo-Byte | -Lo-Byte | -- (0x8000 | 0x7D00 := Nicht vorhanden) | -|
| 19 | -Hi-Byte | -Hi-Byte | -Ionisationsstrom | -24_15_0 | -
| 20 | -Lo-Byte | -Lo-Byte | -||
| 21 | -FF | -FF | -Anlagendruck am Wärmeerzeuger | -24_17_0 | -
| - (FF := ungültig) | -||||
| 22 | -Hi-Byte | -Hi-Byte | -Displaycode | -24_18_0 | -
| 23 | -Lo-Byte | -Lo-Byte | -||
| 24 | -Hi-Byte | -Hi-Byte | -Cause Code | -24_20_0 | -
| 25 | -Lo-Byte | -Lo-Byte | -||
| 26 | -00 | -FF | -Warmwasserdurchfluss-Menge | -24_22_0 | -
| - (FF := ungültig) | -||||
| 27 | -Bit0...Bit7 | -Bit0...Bit7 | -Status 2 | -|
| Bit0 | -Bit0 | -- Status Speicherlade-Pumpe (SP) | -24_23_0 | -|
| Bit1 | -Bit1 | -- Flüssiggasventil an | -24_23_1 | -|
| Bit2 | -Bit2 | -- Status Gaswärmepumpe | -24_23_2 | -|
| Bit3 | -Bit3 | -- Status d. Relais im Schaltmodul UM10 | -24_23_3 | -|
| Bit4 | -Bit4 | -- Zirkulationspumpe an (Relais-Signal f. ZP) | -24_23_4 | -|
| Bit5 | -Bit5 | -- Status Brenner Relais | -24_23_5 | -|
| Bit6 | -Bit6 | -- FB reservierte Bit | -24_23_6 | -|
| Bit7 | -Bit7 | -- FB reservierte Bit | -24_23_7 | -|
| 28 | -Bit0...Bit7 | -Bit0...Bit7 | -Status 3 | -|
| Bit0 | -Bit0 | -- Status der Füllfunktion | -24_24_0 | -|
| Bit1 | -Bit1 | -- Status Schaltmodul UM10 | -24_24_1 | -|
| Bit2 | -Bit2 | -- UM10 Signal für Brenner-Blockierung | -24_24_2 | -|
| Bit3 | -Bit3 | -- Brennerfreigabe durch Schaltmodul | -24_24_3 | -|
| Bit4 | -Bit4 | -- Status Brenneranlauf im Schaltmodul | -24_24_4 | -|
| Bit5 | -Bit5 | -- Heizbetrieb blockiert bei Heatronic III | -24_24_5 | -|
| Bit6 | -Bit6 | -- STB – Test aktiv | -24_24_6 | -|
| Bit7 | -Bit7 | -- Tastensperre ein | -24_24_7 | -|
| 29 | -<CRC> | -Hi-Byte | -CRC | Hi-Byte - Ansauglufttemperatur | -xy | 24_25_0 | -
| 30 | -<Ende> | -Lo-Byte | -Ende | Lo-Byte - Ansauglufttemperatur | -|
| 31 | -– | -<CRC> | --– | CRC | -|
| 32 | -– | -<Ende> | -–- | Ende | -|
| HT Bus-Telegramme | -|||
| Message-ID:25_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 33Byte | -|||
| Kessel-Telegramm: Heizgerät | -|||
| 0 | -88 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -19 | -25_x_0 | -|
| 3 | -xy | -Telegramm-Offset (hier 0...25). | -|
| 4 | -Hi-Byte | -Außentemperatur | -25_0_0 | -
| 5 | -Lo-Byte | -||
| 6 | -Hi-Byte | -Maximale Temperatur | -25_2_0 | -
| 7 | -Lo-Byte | -- 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|
| - 0x7FFF = Sensorkurzschluss | -|||
| 8 | -Hi-Byte | -Abgastemperatur | -25_4_0 | -
| 9 | -Lo-Byte | -- 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|
| - 0x7FFF = Sensorkurzschluss | -|||
| 10 | -Hi-Byte | -Gasdruck / Luftdruck | -25_6_0 | -
| 11 | -Lo-Byte | -- 0xFFFF = Sensorunterbrechung / Fühler nicht vorhanden | -|
| 12 | -xy | -Taktsperre im Zweipunkt Betrieb | -25_8_0 | -
| 13 | -xy | -Modulationsbereich Heizungspumpe (HP) | -25_9_0 | -
| 14 | -Byte 3 | -Brennerstarts Total (für Warmwasser und Heizung) | -25_10_0 | -
| 15 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 16 | -Byte 1 | -„ | -|
| 17 | -Byte 3 | -Betriebsminuten Brenner Total (für Warmwasser und Heizung) | -25_13_0 | -
| 18 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 19 | -Byte 1 | -„ | -|
| 20 | -Byte 3 | -Betriebszeit f. Zweite Brennerstufe | -25_16_0 | -
| 21 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 22 | -Byte 1 | -„ | -|
| 23 | -Byte 3 | -Betriebsminuten Brenner (nur Heizung) | -25_19_0 | -
| 24 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 25 | -Byte 1 | -„ | -|
| 26 | -Byte 3 | -Brennerstarts (nur Heizung) | -25_22_0 | -
| 27 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 28 | -Byte 1 | -„ | -|
| 29 | -Hi-Byte | -Temperatur an hydraulischer Weiche | -25_25_0 | -
| 30 | -Lo-Byte | -- 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|
| - 0x7FFF = Sensorkurzschluss | -|||
| 31 | -<CRC> | -CRC | -|
| 32 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:188_x_y | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| Kessel-Telegramm: Heizgerät | -|||
| 0 | -88 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -BC | -188_x_y | -|
| 3 | -xy | -Telegramm-Offset (hier 0...13). | -|
| 4 | -Hi-Byte | -Temperatur Puffer-Speicher oben | -188_0_0 | -
| 5 | -Lo-Byte | -||
| 6 | -Hi-Byte | -Temperatur Puffer-Speicher unten | -188_2_0 | -
| 7 | -Lo-Byte | -||
| 8 | -Hi-Byte | -Temperatur Vorlauf Verflüssiger | -188_4_0 | -
| 9 | -Lo-Byte | -||
| 10 | -Hi-Byte | -Temperatur Rücklauf Verflüssiger | -188_6_0 | -
| 11 | -Lo-Byte | -||
| 12 | -Bit0...Bit7 | -Betriebs-Status1 | -|
| Bit0 | -- Wärmepumpe | -188_8_0 | -|
| Bit1 | -188_8_1 | -||
| Bit2 | -188_8_2 | -||
| Bit3 | -188_8_3 | -||
| Bit4 | -- Status Abtaumöglichkeit an W-Pumpe | -188_8_4 | -|
| Bit5 | -188_8_5 | -||
| Bit6 | -188_8_6 | -||
| Bit7 | -188_8_7 | -||
| 13 | -Bit0...Bit7 | -Betriebs-Status2 | -|
| Bit0 | -- Abtaufunktion an W-Pumpe | -188_9_0 | -|
| Bit1 | -- Status Verdichter | -188_9_1 | -|
| Bit2 | -- Fehlerstatus Wärmepumpe | -188_9_2 | -|
| Bit3 | -188_9_3 | -||
| Bit4 | -188_9_4 | -||
| Bit5 | -188_9_5 | -||
| Bit6 | -188_9_6 | -||
| Bit7 | -188_9_7 | -||
| 14 | -<CRC> | -CRC | -|
| 15 | -<Ende> | -Ende | -|
| HT Bus-Telegramme | -|||
| Message-ID:27_0_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 7Byte | -|||
| Telegramm: Solltemperatur WW-System | -|||
| 0 | -90 | -- | Source | -
| 1 | -00 | -Target | -|
| 2 | -1B | -27_x_0 | -|
| 3 | -00 | -Immer 00 | -|
| 4 | -32 | -Sollwert Warmwasser-Temperatur | -27_0_0 | -
| 5 | -<CRC> | -CRC | -|
| 6 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID: 51_x_y | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| Kessel-Telegramm: Warmwasser | -|||
| 0 | -88 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -33 | -51_x_y | -|
| 3 | -xy | -Telegramm-Offset (hier 0...12). | -|
| 4 | -xy | -Soll-Temperatur Warmwasser | -51_0_0 | -
| 5 | -xy | -51_1_0 | -|
| 6 | -xy | -Soll-Temperatur Warmwasser | -51_2_0 | -
| 7 | -xy | -Temperaturhysterese bei T-Soll | -51_3_0 | -
| 8 | -xy | -51_4_0 | -|
| 9 | -xy | -51_5_0 | -|
| 10 | -xy | -51_6_0 | -|
| 11 | -xy | -51_7_0 | -|
| 12 | -xy | -51_8_0 | -|
| 13 | -xy | -51_9_0 | -|
| 14 | -xy | -51_10_0 | -|
| 15 | -xy | -51_11_0 | -|
| 16 | -xy | -51_12_0 | -|
| 17 | -<CRC> | -||
| 18 | -<Ende> | -||
| HT Bus-Telegramme | -|||||
| Message-ID: 52_x_y | -|||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -||
| 23Byte | -22Byte | -25Byte | -|||
| Kessel-Telegramm: Warmwasser | -|||||
| 0 | -88 | -88 | -88 | -Source | -|
| 1 | -00 | -00 | -00 | -Target | -|
| 2 | -34 | -34 | -34 | -52_x_y | -|
| 3 | -xy | -xy | -xy | -Telegramm-Offset (hier 0...17). | -|
| 4 | -xy | -xy | -xy | -Soll-Temperatur Warmwasser | -52_0_0 | -
| 5 | -Hi-Byte | -Hi-Byte | -Hi-Byte | -Ist-Temperatur Warmwasser | -52_1_0 | -
| 6 | -Lo-Byte | -Lo-Byte | -Lo-Byte | -- 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|
| - 0x7FFF = Sensorkurzschluss | -|||||
| 7 | -Hi-Byte | -Hi-Byte | -Hi-Byte | -Ist-Temperatur im Warmwasser - Speicher | -52_3_0 | -
| 8 | -Lo-Byte | -Lo-Byte | -Lo-Byte | -- 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|
| - 0x7FFF = Sensorkurzschluss | -|||||
| 9 | -Bit0...Bit7 | -Bit0...Bit7 | -Bit0...Bit7 | -Warmwasser-Status | -|
| Bit0 | -Bit0 | -Bit0 | -- WW-Bereitung im Normalbetrieb | -52_5_0 | -|
| Bit1 | -Bit1 | -Bit1 | -- Einmalige Speicher-Ladung | -52_5_1 | -|
| Bit2 | -Bit2 | -Bit2 | -- Thermische Desinfektion | -52_5_2 | -|
| Bit3 | -Bit3 | -Bit3 | -- Speicherladung im WW-System | -52_5_3 | -|
| Bit4 | -Bit4 | -Bit4 | -- Speicherladung im Nachwärmsystem | -52_5_4 | -|
| Bit5 | -Bit5 | -Bit5 | -- Erreichter Sollwert Warmwasser-Temperatur | -52_5_5 | -|
| Bit6 | -Bit6 | -Bit6 | -- Warmwasserbetrieb | -52_5_6 | -|
| Bit7 | -Bit7 | -Bit7 | -- Status f. Art der Warmwasserbereitung | -52_5_7 | -|
| -- 0 = Warmwasserteilvorrang | -|||||
| -- 1 = Warmwasservorrang | -|||||
| 10 | -Bit0...Bit7 | -Bit0...Bit7 | -Bit0...Bit7 | -WW-Fehlersignale | -|
| Bit0 | -Bit0 | -Bit0 | -- WW-Temperaturfühler 1 defekt | -52_6_0 | -|
| Bit1 | -Bit1 | -Bit1 | -- WW-Temperaturfühler 2 defekt | -52_6_1 | -|
| Bit2 | -Bit2 | -Bit2 | -- WW-System wird nicht aufgeheizt | -52_6_2 | -|
| Bit3 | -Bit3 | -Bit3 | -- Thermische Desinfektion ist nicht in Betrieb | -52_6_3 | -|
| Bit4 | -Bit4 | -Bit4 | -- WW ist nicht blockiert | -52_6_4 | -|
| Bit5...Bit7 | -Bit5...Bit7 | -Bit5...Bit7 | -- Immer 0 | -52_6_5 bis | -|
| 52_6_7 | -|||||
| 11 | -Bit0...Bit7 | -Bit0...Bit7 | -Bit0...Bit7 | -Zirkulationspumpen-Status | -|
| Bit0 | -Bit0 | -Bit0 | -- Zirkulationspumpe (ZP) im Normalbetrieb | -52_7_0 | -|
| Bit1 | -Bit1 | -Bit1 | -- Zirkulationspumpe (ZP) an bei einmaliger Speicherladung | -52_7_1 | -|
| Bit2 | -Bit2 | -Bit2 | -- Zirkulationspumpe (ZP) an | -52_7_2 | -|
| Bit3 | -Bit3 | -Bit3 | -- Ansteuersignal f. Zirkulationspumpe (ZP) | -52_7_3 | -|
| Bit4...Bit7 | -Bit4...Bit7 | -Bit4...Bit7 | -- Immer 0 | -||
| 12 | -0...4 | -0...4 | -0...4 | -Bauart des Warmwassersystems | -52_8_0 | -
| - 0 = ohne Warmwasserbereitung | -|||||
| - 1 = nach Durchlaufprinzip | -|||||
| - 2 = Druckloser Speicher | -|||||
| - 3 = Warmwasser-Speicherprinzip | -|||||
| - 4 = Schichtlade-Speicher | -|||||
| 13 | -xy | -xy | -xy | -Aktuelle Wasserduchflussmenge | -52_9_0 | -
| 14 | -Byte 3 | -Byte 3 | -Byte 3 | -Betriebszeit Warmwasser-Erzeugung (Minuten) | -52_10_0 | -
| 15 | -Byte 2 | -Byte 2 | -Byte 2 | -||
| 16 | -Byte 1 | -Byte 1 | -Byte 1 | -||
| 17 | -Byte 3 | -Byte 3 | -Byte 3 | -Anzahl Brennerstarts für Warmwassererzeugung | -52_13_0 | -
| 18 | -Byte 2 | -Byte 2 | -Byte 2 | -||
| 19 | -Byte 1 | -Byte 1 | -Byte 1 | -||
| 20 | -xy | -<CRC> | -xy | -Modulationsbereich ZP im WW-System 1 | -52_16_0 | -
| 21 | -<CRC> | -<Ende> | -Hi-Byte | -Hi-Byte Warmwasser Eingangstemperatur | -52_17_0 | -
| 22 | -<Ende> | --- | -Lo-Byte | -Lo-Byte Warmwasser Eingangstemperatur | -|
| - 0x8000 = Sensorunterbrechung / Fühler nicht vorhanden | -|||||
| - 0x7FFF = Sensorkurzschluss | -|||||
| 23 | -<CRC> | -||||
| 24 | -<Ende> | -||||
| HT Bus-Telegramme | -|||
| Message-ID:467_x_0 bis 468_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 11Byte | -|||
| Telegramm: Betriebsart WW-System | -|||
| 0 | -90 | -- | Source | -
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -D3 / D4 | -WW-System | -|
| - D3=WW-System1 | -467_0_0 | -||
| - D4=WW-System2 | -468_0_0 | -||
| 6 | -xy | -Betriebsart Warmwasser-System | -|
| - 0=Automatikbetrieb f. WW-Speicher | -|||
| - 1=Automatikbetrieb b. Kombigerät aktiv | -|||
| - 2=Automatikbetrieb b. Kombigerät ausgeschaltet | -|||
| - 3=Automatikbetrieb i. Urlaubsmodus f. WW-Speicher | -|||
| - 4=Urlaubsfunktion eingeschaltet a. Kombigerät | -|||
| - 5=Urlaubsfunktion ausgeschaltet a. Kombigerät | -|||
| - 6=Fest eingestellte Speichertemperatur im Urlaubsprogramm | -|||
| - 7=Thermische Desinfektion f. WW-Speicher | -|||
| - 8=Warmwasser sofort | -|||
| - 9=Estrichtrocknung in Betrieb oder angehalten | -|||
| 7 | -xy | -Wert f. Temperaturreduzierung bei solarer Unterstuetzung | -467_1_0 bis 468_1_0 | -
| 8 | -xy | -Status der letzten thermischen Desinfektion | -467_2_0 bis 468_2_0 | -
| - 0=Abgeschlossen | -|||
| - 1=In Betrieb | -|||
| - 2=Abgebrochen | -|||
| 9 | -<CRC> | -CRC | -|
| 10 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -||||
| Message-ID:26_x_0 | -||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -Beispiel (Hex) | -
| 11Byte | -||||
| Telegramm: Heizkreis Systemwerte | -||||
| 0 | -90 | -Source | -||
| 1 | -08 | -Target = Steuerung | -Target | -|
| 2 | -1A | -Immer 1A | -26_x_0 | -|
| 3 | -xy | -Telegramm-Offset (hier 0...4). | -||
| 4 | -26 | -Sollwert f. Vorlauftemperatur im Heizkreis | -26_0_0 | -|
| 5 | -64 | -Maximale Leistung des Wärmeerzeugers | -26_1_0 | -|
| 6 | -64 | -Sollwert f. Drehzahl der Umwälzpumpe | -26_2_0 | -|
| 7 | -0 / FF | -Status f. Aufheizen mit hohem Wirkungsgrad | -26_3_0 | -|
| 8 | -3 | -Betriebsart f. Umwälzpumpe im Energiesparmodus | -26_4_0 | -|
| 9 | -<CRC> | -CRC | -||
| 10 | -<Ende> | -Ende Marker | -||
| HT Bus-Telegramme | -|||
| Message-ID:268_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 14Byte | -|||
| IPM – Telegramm (Schaltmodul) | -|||
| 0 | -A0...A7 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -0C | -Immer 0C | -EMS Type(L) | -
| 6 | -0...2 | -Bauart des Heizkreises (Mischer ja/nein) | -|
| - 0=Nicht vorhanden | -|||
| - 1=Ungemischter Heizkreis | -268_0_0 | -||
| - 2=Gemischter Heizkreis | -268_0_1 | -||
| 7 | -0...1 | -Status Heizungspumpe im Heizkreis | -268_1_0 | -
| - 0=Pumpe aus | -|||
| - 1=Pumpe Ein | -|||
| 8 | -xy | -Mischer Position (Prozentwert) | -268_2_0 | -
| 9 | -Hi-Byte | -Vorlauftemperatur 'Ist' für gemischten Heizkreis | -268_3_0 | -
| 10 | -Lo-Byte | -||
| 11 | -xy | -Sollwert Vorlauftemperatur (Grad) | -268_5_0 | -
| 12 | -<CRC> | -CRC | -|
| 13 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:296_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 32Byte | -|||
| Telegramm: Heizkreis Fehlermeldungen | -|||
| 0 | -90 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -Offset auf nächste Fehlermeldung | -EMS Offset | -
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -28 | -Fehler | -EMS Type(L) | -
| 6 | -xy1 | -Fehler1: Display-Code1 | -296_0_0 | -
| 7 | -xy2 | -Fehler1: Display-Code2 | -296_1_0 | -
| 8 | -Hi-Byte | -Fehler1: Fehlercode | -296_2_0 | -
| 9 | -Lo-Byte | -||
| 10 | -xy | -Fehler1: Jahr (+2000) | -296_4_0 | -
| 11 | -xy | -Fehler1: Monat | -296_5_0 | -
| 12 | -xy | -Fehler1: Stunde | -296_6_0 | -
| 13 | -xy | -Fehler1: Tag | -296_7_0 | -
| 14 | -xy | -Fehler1: Minute | -296_8_0 | -
| 15 | -Hi-Byte | -Fehler1: Minute (Reserviert) | -296_9_0 | -
| 16 | -Lo-Byte | -||
| 17 | -xy | -Fehler1: Busadresse | -296_11_0 | -
| 18 | -xy1 | -Fehler2: Display-Code1 | -296_12_0 | -
| 19 | -xy2 | -Fehler2: Display-Code2 | -296_13_0 | -
| 20 | -Hi-Byte | -Fehler2: Fehlercode | -296_14_0 | -
| 21 | -Lo-Byte | -||
| 22 | -xy | -Fehler2: Jahr (+2000) | -296_16_0 | -
| 23 | -xy | -Fehler2: Monat | -296_17_0 | -
| 24 | -xy | -Fehler2: Stunde | -296_18_0 | -
| 25 | -xy | -Fehler2: Tag | -296_19_0 | -
| 26 | -xy | -Fehler2: Minute | -296_20_0 | -
| 27 | -Hi-Byte | -Fehler2: Minute (Reserviert) | -296_21_0 | -
| 28 | -Lo-Byte | -||
| 29 | -xy | -Fehler2: Busadresse | -296_23_0 | -
| 30 | -<CRC> | -CRC | -|
| 31 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:357_x_0 bis 366_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 29Byte | -|||
| Telegramm: Heizkreis Steuerung | -|||
| (Bauart des Heizkreises) | -|||
| 0 | -90 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -65...6E | -Heizkreis x | -EMS Type(L) | -
| 65 | -65=Heizkreis1 | -357_0_0 | -|
| 66 | -66=Heizkreis2 | -358_0_0 | -|
| 67 | -67=Heizkreis3 | -359_0_0 | -|
| 68 | -68=Heizkreis4 | -360_0_0 | -|
| 69 | -69=Heizkreis5 | -361_0_0 | -|
| 6A | -6A=Heizkreis6 | -362_0_0 | -|
| 6B | -6B=Heizkreis7 | -363_0_0 | -|
| 6C | -6C=Heizkreis8 | -364_0_0 | -|
| 6D | -6D=Heizkreis9 | -365_0_0 | -|
| 6E | -6E=Heizkreis10 | -366_0_0 | -|
| 6 | -0...3 | -Bauart-Werte | -357_1_0 bis | -
| - 0=Nicht vorhanden | -366_1_0 | -||
| - 1=Ungemischter Heizkreis ohne Schaltmodul IPM | -|||
| - 2=Ungemischter Heizkreis mit Schaltmodul IPM | -|||
| - 3=Gemischter Heizkreis | -|||
| 7 | -0...2 | -Fernbedienung für Heizkreis x | -|
| - 0=Nicht vorhanden | -|||
| - 1=Fernbedienung FB 10 | -|||
| - 2=Fernbedienung FB100 | -|||
| 8 | -0...4 | -Bauart des Heizkreis x | -|
| - 0=nicht definiert | -357_2_0 bis | -||
| - 1=Fußpunkt/Endpunkt | -366_2_0 | -||
| - 2=Radiatoren | -|||
| - 3=Konvektoren | -|||
| - 4=Fußbodenheizung | -|||
| 9 | -z.B. 19 | -Fußpunkt für Heizkurve (in Grad) | -357_3_0 bis | -
| 366_3_0 | -|||
| 10 | -z.B. 30 | -Endpunkt für Heizkurve (in Grad) | -357_4_0 bis | -
| 366_4_0 | -|||
| 11 | -z.B. 50 | -Maximale Vorlauftemperatur (in Grad) für Heizkreis x | -357_5_0 bis | -
| 366_5_0 | -|||
| 12 | -Raumeinfluss-Faktor (%) im Heizkreis x | -357_6_0 bis | -|
| 366_6_0 | -|||
| 13 | -0...2 | -Raumeinfluss im Heizkreis x bei Betriebsart | -357_7_0 bis | -
| - 0=nicht definiert | -366_7_0 | -||
| - 1=Normalbetrieb / Sparbetrieb / Frostschutzbetrieb | -|||
| - 2=Sparbetrieb / Frostschutzbetrieb | -|||
| 14 | -Einstellung dauerhafte Raumtemperatur-Korrektur im Heizkreis x | -357_8_0 bis | -|
| 366_8_0 | -|||
| 15 | -0...3 | -Betriebsart Raumtemperaturfühler für Heizkreis x | -357_9_0 bis | -
| - 0=nicht definiert | -366_9_0 | -||
| - 1=Externer Temperaturfühler | -|||
| - 2=Interner Temperaturfühler | -|||
| - 3=Temperatur im Sparmodus | -|||
| 16 | -0/FF | -Status für Temperaturniveau Frost | -357_10_0 bis | -
| - 0 = Aus | -366_10_0 | -||
| - FF = Ein | -|||
| 17 | -z.B. 2B | -Abschaltung (Außentemperaturgesteuert) von Heizkreis x | -357_11_0 bis | -
| - (in 0.5 Grad Schritten) | -366_11_0 | -||
| 18 | -Frostgrenztemperatur für Heizkreis x | -357_12_0 bis | -|
| - (in 0.5 Grad Schritten) | -366_12_0 | -||
| 19 | -0...6 | -Aktives Heizprogramm im Heizkreis x | -357_13_0 bis | -
| - 0=nicht definiert | -366_13_0 | -||
| - 1-6=Nummer des aktiven Heizprogramms | -|||
| - (1:A; 2:=B;3:=C; …) | -|||
| 20 | -0....4 | -Betriebsart für den Heizkreis x | -357_14_0 bis | -
| - 0=nicht definiert | -366_14_0 | -||
| - 1=Betrieb im Frostschutzmodus | -|||
| - 2=Betrieb im Sparmodus | -|||
| - 3=Betrieb im Normalmodus | -|||
| - 4=Automatikbetrieb | -|||
| 21 | -z.B. 14 | -Temperaturniveau für Betriebsart Frost im Heizkreis x | -357_15_0 bis | -
| - (in 0.5 Grad Schritten) | -366_15_0 | -||
| 22 | -z.B. 28 | -Temperaturniveau für Betriebsart Sparen im Heizkreis x | -357_16_0 bis | -
| - (in 0.5 Grad Schritten) | -366_16_0 | -||
| 23 | -z.B. 2B | -Temperaturniveau für Betriebsart Normal im Heizkreis x | -357_17_0 bis | -
| - (in 0.5 Grad Schritten) | -366_17_0 | -||
| 24 | -0...3 | -Aufheizgeschwindigkeit für Heizkreis x | -357_18_0 bis | -
| - 0=nicht definiert | -366_18_0 | -||
| - 1=Langsam | -|||
| - 2=Normal | -|||
| - 3=Schnell | -|||
| 25 | -0...4 | -Urlaubsprogramm Betriebsart für Heizkreis x | -357_19_0 bis | -
| - 0=nicht definiert | -366_19_0 | -||
| - 1=Betrieb im Frostschutzmodus | -|||
| - 2=Betrieb im Sparmodus | -|||
| - 3=Betrieb im Normalmodus | -|||
| - 4=Automatikbetrieb | -|||
| 26 | -Optimierungseinfluss für solare Unterstützung im Heizkreis x | -357_20_0 bis | -|
| - (in 1 Grad Schritten) | -366_20_0 | -||
| 27 | -<CRC> | -CRC | -|
| 28 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||||
| Message-ID:367_x_0 bis 376_x_0 | -|||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -||
| 17Byte | -14Byte | -9Byte | -|||
| Telegramm: Heizkreis Steuerung | -|||||
| (Temperaturniveau für den Heizkreis) | -|||||
| 0 | -90 | 9x | -90 | 9x | -90 | 9x | -(wobei: x:= 8...F) | -Source | -
| 1 | -00 | -00 | -00 | -Target | -|
| 2 | -FF | -FF | -FF | -EMS Marker | -|
| 3 | -xy | -xy | -xy | -EMS Offset | -|
| 4 | -00 | -00 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -6F...78 | -6F...78 | -6F...78 | -Heizkreis-Zuordnung | -EMS Type(L) | -
| 6F=Heizkreis1 | -367_0_0 | -||||
| 70=Heizkreis2 | -368_0_0 | -||||
| 71=Heizkreis3 | -369_0_0 | -||||
| 72=Heizkreis4 | -370_0_0 | -||||
| 73=Heizkreis5 | -371_0_0 | -||||
| 74=Heizkreis6 | -372_0_0 | -||||
| 75=Heizkreis7 | -373_0_0 | -||||
| 76=Heizkreis8 | -374_0_0 | -||||
| 77=Heizkreis9 | -375_0_0 | -||||
| 78=Heizkreis10 | -376_0_0 | -||||
| 6 | -0...3 | -0...3 | -0...3 | -Betriebsart Heizung: | -367_0_0 bis | -
| - 0=nicht definiert | -376_0_0 | -||||
| - 1=Frost | -|||||
| - 2=Sparen | -|||||
| - 3=Heizen | -|||||
| 7 | -0...5 | -0...5 | -<CRC> | -Betriebsart Heizkreis | | CRC | -367_1_0 bis | -
| - 0=nicht definiert | -376_1_0 | -||||
| – | -- 1=dauernd | -||||
| – | -- 2=Automatikbetrieb | -||||
| – | -- 3=Urlaub | -||||
| – | -- 4=Estrichtrocknung im StandbyModus | -||||
| – | -- 5=Estrichtrocknung in Betrieb | -||||
| 8 | -Hi-Byte | -Hi-Byte | -<Ende> | -Soll-Temperatur (HK1 bis HK10) | | Ende Marker | -367_2_0 bis | -
| 9 | -Lo-Byte | -Lo-Byte | -– | -376_2_0 | -|
| 10 | -Hi-Byte | -Hi-Byte | -– | -Ist-Temperatur (HK1 bis HK10 vom Regler) | -367_4_0 bis | -
| 11 | -Lo-Byte | -Lo-Byte | -– | -376_4_0 | -|
| 12 | -Hi-Byte | -<CRC> | -– | -T-Raum FB10x | CRC | -367_6_0 | -
| 13 | -Lo-Byte | -<Ende> | -– | -T-Raum FB10x | Ende Marker | -|
| 14 | -00 … 07 | -– | -– | -Temperaturwert für solare Unterstützung der Vorlauftemperatur | -367_8_0 | -
| 15 | -<CRC> | -– | -– | -CRC | -|
| 16 | -<Ende> | -– | -– | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:377_x_0 bis 386_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 19Byte | -|||
| Telegramm: Heizkreis Steuerung | -|||
| 0 | -90 | -(Bauart des Heizkreises) | -Source | -
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -79...82 | -Heizkreis x Kennung | -EMS Type(L) | -
| 79=Heizkreis1 | -377_0_0 | -||
| 7A=Heizkreis2 | -378_0_0 | -||
| 7B=Heizkreis3 | -379_0_0 | -||
| 7C=Heizkreis4 | -380_0_0 | -||
| 7D=Heizkreis5 | -381_0_0 | -||
| 7E=Heizkreis6 | -382_0_0 | -||
| 7F=Heizkreis7 | -383_0_0 | -||
| 80=Heizkreis8 | -384_0_0 | -||
| 81=Heizkreis9 | -385_0_0 | -||
| 82=Heizkreis10 | -386_0_0 | -||
| 6 | -0...3 | -Bauart-Werte | -377_0_0 bis | -
| - 0=Nicht vorhanden | -386_0_0 | -||
| - 1=Ungemischter Heizkreis ohne Schaltmodul IPM | -|||
| - 2=Ungemischter Heizkreis mit Schaltmodul IPM | -|||
| - 3=Gemischter Heizkreis | -|||
| 7 | -Anpassungsfaktor im Heizkreis x | -377_1_0 bis | -|
| 386_1_0 | -|||
| 8 | -Verstärkungsfaktor im Heizkreis x | -377_2_0 bis | -|
| 386_2_0 | -|||
| 9 | -Maximale Vorlauftemperatur im Heizkreis x | -377_3_0 bis | -|
| 386_3_0 | -|||
| 10 | -0...4 | -Betriebsart für Heizkreis x | -377_4_0 bis | -
| - 0=nicht definiert | -386_4_0 | -||
| - 1=Betrieb im Frostschutzmodus | -|||
| - 2=Betrieb im Sparmodus | -|||
| - 3=Betrieb im Normalmodus | -|||
| - 4=Automatikbetrieb | -|||
| 11 | -Temperaturniveau bei Betriebsart Frost | -377_5_0 bis | -|
| - (in 0.5 Grad Schritten) | -386_5_0 | -||
| 12 | -Temperaturniveau bei Betriebsart Sparen | -377_6_0 bis | -|
| - (in 0.5 Grad Schritten) | -386_6_0 | -||
| 13 | -Temperaturniveau bei Betriebsart Normal | -377_7_0 bis | -|
| - (in 0.5 Grad Schritten) | -386_7_0 | -||
| 14 | -Urlaubsprogramm Betriebsart für Heizkreis x | -377_8_0 bis | -|
| - ( Werte wie bei Byte:10 Betriebsart Heizkreis) | -386_8_0 | -||
| 15 | -0/FF | -Status Optimierungsfunktion im Heizkreis x | -377_9_0 bis | -
| - 0 = Aus | -386_9_0 | -||
| - FF = Ein | -|||
| 16 | -0...6 | -Aktiviertes Heizprogramm | -377_10_0 bis | -
| - 0=Nicht definiert | -386_10_0 | -||
| - 1-6=Nummer des aktiven Heizprogramms | -|||
| - (1=A; 2=B; 3=C; …) | -|||
| 17 | -<CRC> | -CRC | -|
| 18 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:677_x_0 bis 684_x_0 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| Telegramm: Heizkreis Steuerung | -|||
| (Temperaturniveau für den Heizkreis) | -|||
| 0 | -90 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -01 | -Immer 01 | -EMS Type(H) | -
| 5 | -A5...AC | -Heizkreis-Zuordnung | -EMS Type(L) | -
| A5=Heizkreis1 | -677_0_0 | -||
| A6=Heizkreis2 | -678_0_0 | -||
| A7=Heizkreis3 | -679_0_0 | -||
| A8=Heizkreis4 | -680_0_0 | -||
| A9=Heizkreis5 | -681_0_0 | -||
| AA=Heizkreis6 | -682_0_0 | -||
| AB=Heizkreis7 | -683_0_0 | -||
| AC=Heizkreis8 | -684_0_0 | -||
| 6 | -Hi-Byte | -Ist-Raumtemperatur (HK1 bis HK8) | -677_0_0 bis | -
| 7 | -Lo-Byte | -684_0_0 | -|
| 8 | -xy | -Status Heizkreis | -6xy_2_0 | -
| 9 | -xy | -6xy_3_0 | -|
| 10 | -xy | -6xy_4_0 | -|
| 11 | -xy | -6xy_5_0 | -|
| 12 | -xy | -Soll-Raumtemperatur (HK1 bis HK8) | -6xy_6_0 | -
| 13 | -xy | -6xy_7_0 | -|
| 14 | -Hi-Byte | -6xy_8_0 | -|
| 15 | -Lo-Byte | -||
| 16 | -xy | -6xy_10_0 | -|
| 17 | -xy | -Temperatur-Niveau | -6xy_11_0 | -
| 18 | -xy | -6xy_12_0 | -|
| 19 | -Hi-Byte | -6xy_13_0 | -|
| 20 | -Lo-Byte | -||
| 21 | -Hi-Byte | -6xy_15_0 | -|
| 22 | -Lo-Byte | -||
| 23 | -xy | -6xy_17_0 | -|
| 24 | -xy | -6xy_18_0 | -|
| 25 | -xy | -6xy_19_0 | -|
| 26 | -xy | -6xy_20_0 | -|
| 27 | -xy | -Betriebsstatus (HK1 bis HK8) {Auto / Manuell} | -6xy_21_0 | -
| 28 | -Hi-Byte | -6xy_22_0 | -|
| 29 | -Lo-Byte | -||
| 30 | -xy | -6xy_24_0 | -|
| 31 | -xy | -6xy_25_0 | -|
| 32 | -xy | -6xy_26_0 | -|
| 33 | -Hi-Byte | -6xy_27_0 | -|
| 34 | -Lo-Byte | -||
| 35 | -xy | -6xy_29_0 | -|
| 36 | -xy | -6xy_30_0 | -|
| 37 | -<CRC> | -CRC | -|
| 38 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:259_x_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 21Byte | -|||
| ISM Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -03 | -Immer 03 | -EMS Type(L) | -
| 6 | -xy | -Optimierungsfaktor WW mit solarer Unterstützung | -259_0_0 | -
| 7 | -xy | -Optimierungsfaktor Heiz. mit solarer Unterstützung | -259_1_0 | -
| 8 | -Hi-Byte | -Solarertrag in der letzten Stunde (Wh) | -259_2_0 | -
| 9 | -Lo-Byte | -||
| 10 | -Hi-Byte | -Solarkollektor1 Temperatur T1 | -259_4_0 | -
| 11 | -Lo-Byte | -||
| 12 | -Hi-Byte | -Solarspeicher Temperatur T2 | -259_6_0 | -
| 13 | -Lo-Byte | -||
| 14 | -Bit0...Bit7 | -Betriebsart Solarpumpe (1. Kollektorfeld) | -|
| Bit0 | -- Solarpumpe (SP); 0=aus; 1=ein | -259_8_0 | -|
| Bit1 | -- Relaysignal Umwälzpumpe(PE) bei thermischer Desinfektion | -259_8_1 | -|
| Bit2..Bit7 | -- Immer 0 | -||
| 15 | -Bit0...Bit7 | -Solar Systemstatus | -|
| Bit0 | -- Abschaltung 1.Kollektorfeld bei Stagnation | -259_9_0 | -|
| -- 0 =Nein | -|||
| -- 1 =Ja (5 Grad Hysterese) | -|||
| Bit1 | -- Status Temperatur bei thermischer Desinfektion | -259_9_1 | -|
| Bit2 | -- Status Solarspeicher | -259_9_2 | -|
| -- 0 =Nicht voll geladen | -|||
| -- 1 =Voll geladen (2 Grad Hysterese) | -|||
| Bit3-8 | -Immer 0 | -||
| 16 | -Byte 3 | -Laufzeit Solarpumpe (Minuten) | -|
| 17 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -259_10_0 | -
| 18 | -Byte 1 | -„ | -|
| 19 | -<CRC> | -CRC | -|
| 20 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -||||
| Message-ID:260_x_y | -||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -|
| 24Byte | -35Byte | -|||
| ISM Solar-Telegramm | -||||
| 0 | -B0 | -B0 | -Source | -|
| 1 | -00 | -00 | -Target | -|
| 2 | -FF | -FF | -EMS Marker | -|
| 3 | -xy | -xy | -EMS Offset | -|
| 4 | -00 | -00 | -Immer 00 | -EMS Type(H) | -
| 5 | -04 | -04 | -Immer 04 | -EMS Type(L) | -
| 6 | -Hi-Byte T3 | -Hi-Byte T3 | -Temperatur T3 im Pufferspeicher f. Rücklaufanhebung | -260_0_0 | -
| 7 | -Lo-Byte T3 | -Lo-Byte T3 | -||
| 8 | -Hi-Byte | -Hi-Byte | -Heizungsrücklauftemperatur | -260_2_0 | -
| 9 | -Lo-Byte | -Lo-Byte | -||
| 10 | -Hi-Byte T5 | -Hi-Byte T5 | -Temperatur T5 im Pufferspeicher (oben) | -260_4_0 | -
| 11 | -Lo-Byte T5 | -Lo-Byte T5 | -||
| 12 | -Hi-Byte T6 | -Hi-Byte T6 | -Temperatur T6 im Bereitschaftsspeicher (unten) | -260_6_0 | -
| 13 | -Lo-Byte T6 | -Lo-Byte T6 | -||
| 14 | -Hi-Byte | -Hi-Byte | -Temperatur 2. Kollektorfeld | -260_8_0 | -
| 15 | -Lo-Byte | -Lo-Byte | -||
| 16 | -Hi-Byte | -Hi-Byte | -Temperatur TB im Pufferspeicher (oben) | -260_10_0 | -
| 17 | -Lo-Byte | -Lo-Byte | -||
| 18 | -Hi-Byte | -Hi-Byte | -Temperatur TC im Vorrang-/Nachrangspeicher | -260_12_0 | -
| 19 | -Lo-Byte | -Lo-Byte | -||
| 20 | -Hi-Byte | -Hi-Byte | -Temperatur am externen Wärmetauscher f. Solarsystem | -260_14_0 | -
| 21 | -Lo-Byte | -Lo-Byte | -||
| 22 | -<CRC> | -Bit0...Bit7 | -Status 1 | -|
| Bit0 | -- Betriebsart Ventil (DWU) f. Rücklaufanhebung | -260_16_0 | -||
| Bit1 | -- Relaisansteuerung f. Umwälzpumpe Umladesystem | -260_16_1 | -||
| Bit2 | -- Umwälzpumpe (PA) im 2. Kollektorfeld | -260_16_2 | -||
| Bit3 | -- Relaisansteuerung f. Umwälzpumpe (PB) Umladesystem | -260_16_3 | -||
| Bit4 | -- Betriebsart Umwälzpumpe (PC)/Umschaltventil | -260_16_4 | -||
| Bit5 | -- Betriebsart Umwälzpumpe (PD) im Sekundärkreis | -260_16_5 | -||
| Bit6 | -- Relaissignal bei Option F | -260_16_6 | -||
| Bit7 | -- unbenutzt | -260_16_7 | -||
| 23 | -<Ende> | -Bit0...Bit7 | -Status 2 | -|
| Bit0 | -- Ansteuerung Ventil DWU1 f. Rücklaufanhebung | -260_17_0 | -||
| Bit1 | -- Status maximale Temperatur im Umladespeicher | -260_17_1 | -||
| Bit2 | -- Status Umwälzpumpe (PA) im 2.Kollektorfeld (Stagnation) | -260_17_2 | -||
| Bit3 | -- Maximaltemperatur erreicht im WW-Speicher B | -260_17_3 | -||
| Bit4 | -- WW-Speicher geladen | -260_17_4 | -||
| Bit5 | -- Testmodus (Speicherladung Vorrangspeicher) | -260_17_5 | -||
| Bit6 | -- Maximaltemperatur erreicht im WW-Speicher C | -260_17_6 | -||
| Bit7 | -- Testmodus | -260_17_7 | -||
| 24 | -Byte 3 | -Betriebszeit f. Solarmumpe (PA) im zweiten Kollektorfeld | -260_18_0 | -|
| 25 | -Byte 2 | -|||
| 26 | -Byte 1 | -|||
| 27 | -Hi-Byte | -Zeitintervall f. Überprüfung ob Speicher C geladen wird | -260_21_0 | -|
| 28 | -Lo-Byte | -|||
| 29 | -Hi-Byte | -Temperatur TF 1 in Wärmequelle | -260_23_0 | -|
| 30 | -Lo-Byte | -|||
| 31 | -Hi-Byte | -Temperatur TF 2 in Wärmesenke | -260_25_0 | -|
| 32 | -Lo-Byte | -|||
| 33 | -<CRC> | -|||
| 34 | -<Ende> | -|||
| HT Bus-Telegramme | -|||
| Message-ID:866 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -62 | -Immer 62 | -EMS Type(L) | -
| 6 | -Hi-Byte | -Solarkollektor1 Temperatur | -866_0_0 | -
| 7 | -Lo-Byte | -||
| 8 | -Hi-Byte | -Solarspeicher Temperatur unten | -866_2_0 | -
| 9 | -Lo-Byte | -||
| 10 | -Hi-Byte | -Solarspeicher Temperatur mittlerer Sensor | -866_4_0 | -
| 11 | -Lo-Byte | -||
| 12 | -Hi-Byte | -Solarkollektor2 Temperatur | -866_6_0 | -
| 13 | -Lo-Byte | -||
| 14 | -Hi-Byte | -Solarspeicher Beipass Temperatur | -866_8_0 | -
| 15 | -Lo-Byte | -||
| 16 | -Hi-Byte | -Solarspeicher Beipass Return-Temperatur | -866_10_0 | -
| 17 | -Lo-Byte | -||
| 18 | -Hi-Byte | -866_12_0 | -|
| 19 | -Lo-Byte | -||
| 20 | -Hi-Byte | -866_14_0 | -|
| 21 | -Lo-Byte | -||
| 22 | -Hi-Byte | -866_16_0 | -|
| 23 | -Lo-Byte | -||
| 24 | -Hi-Byte | -866_18_0 | -|
| 25 | -Lo-Byte | -||
| 26 | -Hi-Byte | -866_20_0 | -|
| 27 | -Lo-Byte | -||
| 28 | -Hi-Byte | -866_22_0 | -|
| 29 | -Lo-Byte | -||
| 30 | -Hi-Byte | -866_24_0 | -|
| 31 | -Lo-Byte | -||
| 32 | -<CRC> | -||
| 33 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:868_x_y | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -64 | -Immer 64 | -EMS Type(L) | -
| 6 | -xy | -868_0_0 | -|
| 7 | -xy | -868_1_0 | -|
| 8 | -Bit0...Bit7 | -868_2_x | -|
| Bit0 | -868_2_0 | -||
| Bit1 | -868_2_1 | -||
| Bit2 | -868_2_2 | -||
| Bit3 | -868_2_3 | -||
| Bit4 | -868_2_4 | -||
| Bit5 | -868_2_5 | -||
| Bit6 | -868_2_6 | -||
| Bit7 | -868_2_7 | -||
| 9 | -Bit0...Bit7 | -Solar Systemstatus | -868_3_x | -
| Bit0 | -- Abschaltung 1.Kollektorfeld bei Stagnation | -868_3_0 | -|
| -- 0 =Nein | -|||
| -- 1 =Ja | -|||
| Bit1 | --- 1 =Solarspeicher maximale Temperatur erreicht | -868_3_1 | -|
| Bit2 | --- 1 =Solarspeicher minimale Temperatur erreicht | -868_3_2 | -|
| Bit3 | -868_3_3 | -||
| Bit4 | -868_3_4 | -||
| Bit5 | -868_3_5 | -||
| Bit6 | -868_3_6 | -||
| Bit7 | -868_3_7 | -||
| 10 | -xy | -868_4_0 | -|
| 11 | -xy | -868_5_0 | -|
| 12 | -xy | -868_6_0 | -|
| 13 | -xy | -868_7_0 | -|
| 14 | -xy | -868_8_0 | -|
| 15 | -xy | -Aktuelle Solarpumpen – Leistung | -868_9_0 | -
| 16 | -xy | -868_10_0 | -|
| 17 | -xy | -868_11_0 | -|
| 18 | -xy | -868_12_0 | -|
| 19 | -xy | -868_13_0 | -|
| 20 | -xy | -868_14_0 | -|
| 21 | -xy | -868_15_0 | -|
| 22 | -<CRC> | -||
| 23 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:873_x_0 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -69 | -Immer 69 | -EMS Type(L) | -
| 6 | -Byte 4 | -Solarertrag letzte Stunde | -873_0_0 | -
| 7 | -Byte 3 | -„ | -|
| 8 | -Byte 2 | -„ ( Calculation-Type: 4 ) | -|
| 9 | -Byte 1 | -„ | -|
| 10 | -Byte 4 | -Solarertrag aktueller Tag | -873_4_0 | -
| 11 | -Byte 3 | -„ | -|
| 12 | -Byte 2 | -„ | -|
| 13 | -Byte 1 | -„ | -|
| 14 | -Byte 4 | -Solarertrag Summe | -873_8_0 | -
| 15 | -Byte 3 | -„ | -|
| 16 | -Byte 2 | -„ | -|
| 17 | -Byte 1 | -„ | -|
| 18 | -<CRC> | -||
| 19 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:874_x_0 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -6A | -Immer 6A | -EMS Type(L) | -
| 6 | -xy | -874_0_0 | -|
| 7 | -xy | -874_1_0 | -|
| 8 | -xy | -874_2_0 | -|
| 9 | -xy | -874_3_0 | -|
| 10 | -xy | -874_4_0 | -|
| 11 | -xy | -874_5_0 | -|
| 12 | -xy | -874_6_0 | -|
| 13 | -xy | -874_7_0 | -|
| 14 | -xy | -874_8_0 | -|
| 15 | -xy | -874_9_0 | -|
| 16 | -Bit0...Bit7 | -874_10_x | -|
| Bit0 | -874_10_0 | -||
| Bit1 | -874_10_1 | -||
| Bit2 | -- Solarpumpe (SP); 0=aus; 1=ein | -874_10_2 | -|
| Bit3 | -874_10_3 | -||
| Bit4 | -874_10_4 | -||
| Bit5 | -874_10_5 | -||
| Bit6 | -874_10_6 | -||
| Bit7 | -874_10_7 | -||
| 17 | -xy | -874_11_0 | -|
| 18 | -xy | -874_12_0 | -|
| 19 | -xy | -874_13_0 | -|
| 20 | -xy | -874_14_0 | -|
| 21 | -xy | -874_15_0 | -|
| 22 | -<CRC> | -||
| 23 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:910_x_0 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -8E | -Immer 8E | -EMS Type(L) | -
| 6 | -Byte 4 | -Solarertrag letzte Stunde | -910_0_0 | -
| 7 | -Byte 3 | -„ | -|
| 8 | -Byte 2 | -„ ( Calculation-Type: 4 ) | -|
| 9 | -Byte 1 | -„ | -|
| 10 | -Byte 4 | -Solarertrag aktueller Tag | -910_4_0 | -
| 11 | -Byte 3 | -„ | -|
| 12 | -Byte 2 | -„ ( Calculation-Type: 5 ) | -|
| 13 | -Byte 1 | -„ | -|
| 14 | -Byte 4 | -Solarertrag Summe | -910_8_0 | -
| 15 | -Byte 3 | -„ | -|
| 16 | -Byte 2 | -„ ( Calculation-Type: 4 ) | -|
| 17 | -Byte 1 | -„ | -|
| 18 | -<CRC> | -||
| 19 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:913_x_0 | -|||
| Byte | -Bemerkung | -Bedeutung / ID | -|
| MS100 Solar-Telegramm | -|||
| 0 | -B0 | -Source | -|
| 1 | -00 | -Target | -|
| 2 | -FF | -EMS Marker | -|
| 3 | -xy | -EMS Offset | -|
| 4 | -02 | -Immer 02 | -EMS Type(H) | -
| 5 | -91 | -Immer 91 | -EMS Type(L) | -
| 6 | -Byte 4 | -Laufzeit Solarpumpe (Minuten) | -913_0_0 | -
| 7 | -Byte 3 | -„ | -|
| 8 | -Byte 2 | -„ ( Calculation-Type: 2 ) | -|
| 9 | -Byte 1 | -„ | -|
| 10 | -xy | -913_4_0 | -|
| 11 | -xy | -913_5_0 | -|
| 12 | -xy | -913_6_0 | -|
| 13 | -xy | -913_7_0 | -|
| 14 | -xy | -913_8_0 | -|
| 15 | -xy | -913_9_0 | -|
| 16 | -xy | -913_10_0 | -|
| 17 | -xy | -913_11_0 | -|
| 18 | -<CRC> | -||
| 19 | -<Ende> | -||
| HT Bus-Telegramme | -|||
| Message-ID:357_14_0 bis 366_14_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 9Byte | -|||
| Modem-CMD:: Betriebsart setzen | -|||
| 0 | -8D | -Source: Modem | -Source | -
| 1 | -10 | -Target | -Target | -
| 2 | -FF | -EMS-Type | -EMS Marker | -
| 3 | -0E | -EMS Offset | -|
| 4 | -00 | -EMS Type(H) | -|
| 5 | -65...6E | -Heizkreis x | -EMS Type(L) | -
| 65=Heizkreis1 | -|||
| 66=Heizkreis2 | -|||
| 67=Heizkreis3 | -|||
| 68=Heizkreis4 | -|||
| 69=Heizkreis5 | -|||
| 6A=Heizkreis6 | -|||
| 6B=Heizkreis7 | -|||
| 6C=Heizkreis8 | -|||
| 6D=Heizkreis9 | -|||
| 6E=Heizkreis10 | -|||
| 6 | -0...4 | -Heizkreisbetriebsart-Werte | -357_14_0 bis | -
| - 0=Nicht definiert | -366_14_0 | -||
| - 1=Betrieb im Frostschutzmodus | -|||
| - 2=Betrieb im Sparmodus | -|||
| - 3=Betrieb im Normalmodus | -|||
| - 4=Automatikbetrieb | -|||
| 7 | -<CRC> | -CRC | -|
| 8 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||
| Message-ID:377_4_0 bis 386_4_0 | -|||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -
| 9Byte | -|||
| Modem-CMD: Betriebsart setzen | -|||
| 0 | -8D | -Source: Modem | -Source | -
| 1 | -10 | -Target | -Target | -
| 2 | -FF | -EMS-Type | -EMS Marker | -
| 3 | -04 | -EMS Offset | -|
| 4 | -00 | -EMS Type(H) | -|
| 5 | -79...82 | -Heizkreis x Kennung | -EMS Type(L) | -
| 79=Heizkreis1 | -|||
| 7A=Heizkreis2 | -|||
| 7B=Heizkreis3 | -|||
| 7C=Heizkreis4 | -|||
| 7D=Heizkreis5 | -|||
| 7E=Heizkreis6 | -|||
| 7F=Heizkreis7 | -|||
| 80=Heizkreis8 | -|||
| 81=Heizkreis9 | -|||
| 82=Heizkreis10 | -|||
| 6 | -0...4 | -Heizkreisbetriebsart-Werte | -357_4_0 bis | -
| - 0=Nicht definiert | -366_4_0 | -||
| - 1=Betrieb im Frostschutzmodus | -|||
| - 2=Betrieb im Sparmodus | -|||
| - 3=Betrieb im Normalmodus | -|||
| - 4=Automatikbetrieb | -|||
| 7 | -<CRC> | -CRC | -|
| 8 | -<Ende> | -Ende Marker | -|
| HT Bus-Telegramme | -|||||
| Message-ID:357_1x_0 bis 366_1x_0 | -|||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -||
| 9Byte | -Betriebsart | -||||
| Modem-CMD: Temperatur-Niveau setzen (Betriebsart Normal/Sparen/Frost) | -Normal | -Sparen | -Frost | -||
| 0 | -8D | -Source: Modem | -Source | -Source | -Source | -
| 1 | -10 | -Target | -Target | -Target | -Target | -
| 2 | -FF | -EMS-Type | -EMS Marker | -EMS Marker | -EMS Marker | -
| 3 | -11/10/0F | -EMS-Offset | -11 (hex) | -10 (hex) | -F (hex) | -
| 4 | -00 | -EMS Type(H) | -EMS Type(H) | -EMS Type(H) | -|
| 5 | -65...6E | -Heizkreis x | -EMS Type(L) | -EMS Type(L) | -EMS Type(L) | -
| 65=Heizkreis1 | -|||||
| 66=Heizkreis2 | -|||||
| 67=Heizkreis3 | -|||||
| 68=Heizkreis4 | -|||||
| 69=Heizkreis5 | -|||||
| 6A=Heizkreis6 | -|||||
| 6B=Heizkreis7 | -|||||
| 6C=Heizkreis8 | -|||||
| 6D=Heizkreis9 | -|||||
| 6E=Heizkreis10 | -|||||
| 6 | -Temperaturniveau für Betriebsart: y im Heizkreis x | -357_17_0 bis | -357_16_0 bis | -357_15_0 bis | -|
| - (in 0.5 Grad Schritten) | -366_17_0 | -366_16_0 | -366_15_0 | -||
| 7 | -<CRC> | -CRC | -|||
| 8 | -<Ende> | -Ende Marker | -|||
| HT Bus-Telegramme | -|||||
| Message-ID:377_x_0 bis 386_x_0 | -|||||
| Byte | -Werte (Hex) | -Bemerkung | -Bedeutung / ID | -||
| 9Byte | -|||||
| Modem-CMD: Temperatur-Niveau setzen (Betriebsart Normal/Sparen/Frost) | -Normal | -Sparen | -Frost | -||
| 0 | -8D | -Source: Modem | -Source | -Source | -Source | -
| 1 | -10 | -Target | -Target | -Target | -Target | -
| 2 | -FF | -EMS-Type | -EMS Marker | -EMS Marker | -EMS Marker | -
| 3 | -07/06/05 | -EMS-Offset | -7 (hex) | -6 (hex) | -5 (hex) | -
| 4 | -00 | -EMS Type(H) | -EMS Type(H) | -EMS Type(H) | -|
| 5 | -79...82 | -Heizkreis x Kennung | -EMS Type(L) | -EMS Type(L) | -EMS Type(L) | -
| 79=Heizkreis1 | -|||||
| 7A=Heizkreis2 | -|||||
| 7B=Heizkreis3 | -|||||
| 7C=Heizkreis4 | -|||||
| 7D=Heizkreis5 | -|||||
| 7E=Heizkreis6 | -|||||
| 7F=Heizkreis7 | -|||||
| 80=Heizkreis8 | -|||||
| 81=Heizkreis9 | -|||||
| 82=Heizkreis10 | -|||||
| 6 | -0...4 | -Temperaturniveau für Betriebsart: y im Heizkreis x | -377_7_0 bis | -377_6_0 bis | -377_5_0 bis | -
| - (in 0.5 Grad Schritten) | -386_7_0 | -386_6_0 | -386_5_0 | -||
| 7 | -<CRC> | -CRC | -|||
| 8 | -<Ende> | -Ende Marker | -|||